Indicator/Display Status and Corrective Actions for Errors Section 12-3
12-3 Indicator/Display Status and Corrective Actions for Errors
Critical Errors
Note Not applicable to Pre-Ver. 1.0 Controllers. Applicable to unit version 1.0 or
later (including Controllers that support EtherNet/IP).
Indicators/display Error history
MS NS Seven-
segment
display
Name Saved in
nonvolatile
memory
Cause Corrective actions
OFF OFF
OFF None Not sup-
ported
Noise level higher than
expected.
Critical hardware fault
Cycle the power supply and
check operation.
If the problem recurs, the NE1A-
series Controller may be faulty.
Check whether there is any
influence from noise, and take
whatever corrective actions are
required.
Lit red
OFF
Left: H
Right: ---
System Fail-
ure
As much
saved as
possible.
Before operation, the
safety output terminal or
test output terminal was
short-circuited to 24
VDC.
Noise impact more than
expected.
Critical hardware fault
Check the external wiring for
power supply short-circuiting at
the output terminal.
Check whether there is any
influence from noise, and take
whatever corrective actions are
required.
Turn the power OFF and back
ON and check operation. If the
problem recurs, the NE1A-
series Controller may be faulty.
Lit red
OFF
P6 System Fail-
ure
(See note.) A safety output terminal or
test output terminal
shorted to 24-VDC before
operation started.
Check the external wiring for
power supply short-circuiting at
the output terminal.
Turn the power OFF and back
ON and check operation. If the
problem recurs, the NE1A-
series Controller may be faulty.