138
Function Block Editing Section 8-3
8-3 Function Block Editing
Editing of function blocks can be used to set parameters, add optional I/O,
and add comments according to the application.
8-3-1 Function Block Parameter Settings
The following parameters can be set for function blocks depending on the
user application. The parameters that can be set will vary from function block
to function block.
Input type
Discrepancy time
Synchronization time
Function test
Input Type Settings
Single Channel
Dual Channel Equivalent
Dual Channel Complementary
Dual Channel Equivalent (2 Pairs)
Dual Channel Complementary (2 Pairs)
The following truth tables outline the internal evaluations performed by the
NE1A-series Controller for each type of input signal. In the tables, 0 indicates
OFF and 1 indicates ON.
Setting: Single Channel
Setting: Dual Channel Equivalent
Tabs:
Function block parameters
Out point Setting, In/Out
Settings Comments
Input 1
(NC)
Output
Enable
00
11
Input 1
(NC)
Input 2
(NC)
Output
Enable
000
010
100
111

Table of Contents