184
Command Reference: Function Blocks Section 8-5
4. As the workpiece continues advancing, the light from MS11 is no longer in-
terrupted by the workpiece, the muting status is cleared and the Muting
Status will go OFF.
Setup Distances
The following formula shows the minimum distance of D1 required for the mut-
ing sensors to provide effective muting function operation:
Formula 1: D1 < L
L: Length of the workpiece
The following formula shows the maximum distance of d1 required for the
muting sensors to provide effective muting function operation:
Formula 2: V × T1min < d1 < V × T1max
V: Transit speed of the workpiece
T1min: NE1A-series Controller cycle time
T1max: Synchronization time setting time
The default setting is 3 s.
D1 must satisfy formula 1 and d1 must satisfy formula 2 in order for the muting
function to be operate effectively. These distance settings must prevent a
passing person from enabling the muting function. Also, the light curtain and
muting sensors must be setup so that a workpiece passes by all of the muting
sensors before the next workpiece arrives at the muting sensors.