227
Reaction Time Section 11-5
The cycle times read by the Network Configurator will be as follows:
Controller cycle time = 4 ms
I/O refresh cycle time = 4 ms
The cycle time of the NE1A-SCPU02 is 6 ms and the I/O refresh time is 6 ms.
The reaction time is obtained using the following equation:
Reaction time (ms) = Switch reaction time
+ NE1A-SCPU01 local input/local output reaction time
+ Actuator reaction time = Switch reaction time
+ ON/OFF delay time (NE1A-SCPU01) + 4 + 4 × 2 + 2.5
+ Actuator reaction time
= 14.5 + ON/OFF delay time (NE1A-series Controller)
+ Switch reaction time + Actuator reaction time
Note Example 1 above shows the configuration for minimizing reaction time in the
NE1A-series Controllers. The guideline for the minimum reaction time is 15
ms for the NE1A-SCPU01(-V1), 21 ms for the NE1A-SCPU02, 20 ms for the
NE1A-SCPU01-EIP, and 28 ms for the NE1A-SCPU02-EIP. The Controller
cannot be used when a reaction time lower than these values is required from
the Controller by the user system.
Example 2: Remote Input – Local Output
The following example shows calculating the reaction time from a remote
input to a
local output for the NE1A-SCPU01 configuration shown in the illustration.
NE1A-SCPU01 configuration:
Program: 1 Safety Gate Monitor, 1 Reset, 1 E-STOP, 1 AND, 1 External
Device Monitor
Standard Slaves: 2 connections
Safety Master: 1 connection (EPI = 6 ms)
Safety Slaves: None
The cycle times read by the Network Configurator will be as follows:
NE1A-SCPU01 cycle time = 6 ms
I/O refresh cycle time = 6 ms
DeviceNet
NE1A-SCPU01
Switch
Actuator
Safety Connection
Network reaction time = 24 ms
Cycle time = 6 ms
I/O refresh cycle = 6 ms
DST1-ID12SL-1