258
Connection Status Tables Section 12-8
01:080E TUNID Mismatch The TUNID for the Safety Slave monitored by the Safety Master does not
match the TUNID of the Safety Slave itself.
Reset the Safety Slave to default settings then download the correct
device parameters.
If the above remedy does not work, delete then re-register the connec-
tions registered to the Safety Master.
Refer to 3-4-2 Network Numbers in the DeviceNet Safety System Configu-
ration Manual (Z905) for information on TUNIDs.
D0:0002 Safety slave that is com-
munications partner is in
IDLE Mode
The communications partner, a NE1A-series Controller that is functioning
as a safety slave, is in IDLE Mode, so a safety I/O connection cannot be
established. Change the operating mode of the communications partner to
RUN Mode.
D0:0001 IDLE Mode The NE1A-series Controller that is functioning as the safety master is in
IDLE mode, so a safety I/O communications have not been started.
Change the Controller’s operating mode to RUN mode.
Status Countermeasures