Nomenclature and Functions Section 2-1
Seven-segment Display
The 7-segment display indicates the NE1A-series Controller’s node address
during normal conditions, and the error code and the node address of the
error during error conditions. Also, “nd” is displayed during normal conditions
if DeviceNet communications are disabled (i.e., Standalone Mode).
For Controllers that support EtherNet/IP, the error code “n4” is displayed if an
error occurs in EtherNet/IP. In addition, the EtherNet/IP IP address can be dis-
played by pressing the IP address display switch.
• IP Address Display Example: When the IP Address is 192.200.200.2
The IP address is displayed from right to left after the display type.
• Display Type: EtherNet/IP IP Address
• Display Type: EtherNet/IP IP Address when BOOTP is Set
Status Display
Normal conditions with
DeviceNet enabled
Operating mode: RUN mode
Safety I/O communications: Operating or not set.
Shows the NE1A-
series Controller’s
node address
(00 to 63).
Lit
Operating mode: RUN mode
Safety I/O communications: Not operating
Flashing
Operating mode: Self-testing, configuring, or idle Flashing
Normal conditions with
DeviceNet disabled
Operating mode: RUN mode “nd” Lit
Operating mode: Self-testing, configuring, or idle Flashing
Error conditions Critical error Indefinite
Only error code Lit
Abort Only error code Lit
Nonfatal error Alternates between displaying the error
code and the node address where the
error occurred.
300 ms 300 ms 300 ms 300 ms 50 ms 50 ms 50 ms 50 ms
500 ms
OFF OFF OFF
OFF
OFF