SF_MutingPar
C002 49154 Reset Error 2 When the Wait for Reset state was entered, an
undetected change to TRUE in the Reset input
was detected.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
C003 49155 Error Muting lamp An error was detected in the muting lamp.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
CYx4
---
*1
Error Muting sequence A muting sequence error was detected in state
8000, 8011, 8311, 8012, 8021, 8014, 8314, 8122,
8422, 8121, 8112, 8114, or 8414.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Y = Sequence state (forward direction: 6 states,
backward direction: 6 states)
C0x4 = Error occurred in state 8000.
C1x4 = Error occurred in forward direction in
state 8011.
C2x4 = Error occurred in forward direction in
state 8311.
C3x4 = Error occurred in forward direction in
state 8012.
C4x4 = Error occurred in forward direction in
state 8014.
C5x4 = Error occurred in forward direction in
state 8314.
C6x4 = Error occurred in forward direction in
state 8021.
C7x4 = Error occurred in backward direction in
state 8122.
C8x4 = Error occurred in backward direction in
state 8422.
C9x4 = Error occurred in backward direction in
state 8121.
CAx4 = Error occurred in backward direction in
state 8114.
CBx4 = Error occurred in backward direction in
state 8414.
CCx4 = Error occurred in backward direction in
state 8112.
CFx4 = MutingEnable was not detected.
x = Sensor status when the error occurred (4 bits:
LSB = MS_11; MS_12; MS_21; MSB = MS_22).