4-3
4-1 Monitor Mode
4
Functions
Real Frequency Monitor [d008]
When a motor with an encoder is connected to a load, and the PG board (3G3AX-PG01) is used,
this monitor displays the real frequency of the motor (regardless of the control method).
(Display)
In forward rotation: 0.00 to 99.99 : Displays in increments of 0.01 Hz.
100.0 to 400.0 : Displays in increments of 0.1 Hz.
In reverse rotation: -0.0 to -99.9 : Displays in increments of 0.1 Hz.
-100 to -400 : Displays in increments of 1 Hz.
Note 1: To use this monitor, set the number of encoder pulses (P011) and the motor pole number
selection (H004 or H204) correctly.
Note 2: The monitored value does not depend on V/f characteristics selection A044.
Torque Reference Monitor [d009]
When torque control is selected for sensor vector control, this monitor displays the currently entered
torque reference value.
The data LED indicator "%" lights up while the d009 setting is displayed.
(Display)
0. to 200.: Displays in increments of 1%.
Torque Bias Monitor [d010]
When sensor vector control is selected, this monitor displays the torque bias amount currently set
in display code d010.
The data LED indicator "%" lights up while the d010 setting is displayed.
(Display)
-150. to +150.: Displays in increments of 1%.
Output Torque Monitor [d012]
Displays an estimated value of the Inverter's output torque.
The data LED indicator "%" lights up while the d012 setting is displayed.
(Display)
-300. to +300.: Displays in increments of 1%.
Note: This monitor is enabled only when "sensorless vector control", "0-Hz sensorless vector
control" , or "sensor vector control" is selected as the control mode.
Output Voltage Monitor [d013]
Displays the output voltage of the Inverter.
The data LED indicator "V" lights up while the d013 setting is displayed.
(Display)
0.0 to 600.0: Displays in increments of 0.1 V.