4-183
4-4 Communication Function
4
Functions
1266h PID output limit function A078 R/W 0 to 1000 0.1 [s]
1267h PID feedforward selection A079 R/W
0: Disabled
1: Input O
2: Input OI
3: Input O2
1268h Not used 
1269h AVR selection A081 R/W
0: Always ON
1: Always OFF
2: OFF during deceleration
126Ah AVR voltage selection A082 R/W
200-V class: 0 (200)
1 (215)
2 (220)
3 (230)
4 (240)
400-V class: 5 (380)
6 (400)
7 (415)
8 (440)
9 (460)
10 (480)
126Bh Not used 
126Ch Not used 
126Dh RUN mode selection A085 R/W
0: Normal operation
1: Energy-saving operation
2: Automatic operation
126Eh
Energy-saving response/
accuracy adjustment
A086 R/W 0 to 1000 0.1 [%]
126Fh
to
1273h
Not used 
1274h
Acceleration time 2
A092
(HIGH)
R/W
1 to 360000 0.01 [s]
1275h
A092
(LOW)
R/W
1276h
Deceleration time 2
A093
(HIGH)
R/W
1 to 360000 0.01 [s]
1277h
A093
(LOW)
R/W
1278h
2-step acceleration/
deceleration selection
A094 R/W
0: Switched via terminal 2CH
1: Switched by setting
1279h
2-step acceleration
frequency
A095
(HIGH)
R/W
0 to 40000 0.01 [Hz]
127Ah
A095
(LOW)
R/W
127Bh
2-step deceleration
frequency
A096
(HIGH)
R/W
0 to 40000 0.01 [Hz]
127Ch
A096
(LOW)
R/W
Register
No.
Function name
Function
code
R/W Monitor and setting parameters
Resolution

Table of Contents