4-187
4-4 Communication Function
4
Functions
1319h Overload limit selection 2 b024 R/W
0: Disabled
1: Enabled during acceleration/
constant speed
2: Enabled during constant speed
3: Enabled during acceleration/constant
speed (accelerated during regenera-
tion)
131Ah Overload limit level 2 b025 R/W
200 to 2000 ( 0.4 to 55 kW)
200 to 1800 (75 to 132 kW)
0.1 [%]
131Bh Overload limit parameter 2 b026 R/W 10 to 3000 0.01 [s]
131Ch
Overcurrent suppression
function
b027 R/W
0: Disabled
1: Enabled
131Dh
Active Frequency Match-
ing restart level
b028 R/W
200 to 2000 ( 0.4 to 55 kW)
200 to 1800 (75 to 132 kW)
0.1 [%]
131Eh
Active Frequency Match-
ing restart parameter
b029 R/W 10 to 3000 0.01 [s]
131Fh
Starting frequency at
Active Frequency Match-
ing restart
b030 R/W
0: Frequency at interruption
1: Max. frequency
2: Set frequency
1320h Soft lock selection b031 R/W
0: Data other than b031 cannot be
changed when terminal SFT is ON.
1: Data other than b031 and the specified
frequency parameter cannot be
changed when terminal SFT is ON.
2: Data other than b031 cannot be
changed.
3: Data other than b031 and the specified
frequency parameter cannot be
changed.
10: Data can be changed during RUN.
1321h Not used
1322h Not used
1323h
RUN time/Power ON time
setting
b034
(HIGH)
R/W
0 to 65535 1 [10 h]
1324h
b034
(LOW)
R/W
1325h
Rotation direction limit
selection
b035 R/W
0: Forward/Reverse enabled
1: Forward only
2: Reverse only
1326h
Reduced voltage startup
selection
b036 R/W
0: (Reduced voltage startup time: Short)
to
255: (Reduced voltage startup time:
Long)
1327h Display selection b037 R/W
0: Complete display
1: Individual display of functions
2: User setting + b037
3: Data comparison display
4: Basic display
Register
No.
Function name
Function
code
R/W Monitor and setting parameters
Resolution