3-43
3-7 Parameter List
3
Operation
Level and output terminal status
C055
Overtorque level
(Forward power
running)
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
100. No %
4-98
C056
Overtorque level
(Reverse
regeneration)
100. No %
C057
Overtorque level
(Reverse power
running)
100. No %
C058
Overtorque level
(Forward
regeneration)
100. No %
C061
Thermal warning
level
0. to 100. 80. No % 4-46
C062 Alarm code selection
00: Disabled
01: 3-bit
02: 4-bit
00 No 4-99
C063 0 Hz detection level
0.00 to 99.99
100.0
0.00 No Hz 4-99
C064
Fin overheat warning
level
0. to 200. 120. No C4-103
Communication function
C071
Communication
speed selection
(Baud rate selection)
02: Loop-back test
03: 2400 bps
04: 4800 bps
05: 9600 bps
06: 19200 bps
04 No
4-140
C072
Communication
station No. selection
1. to 32. 1. No
C073
Communication bit
length selection
7: 7-bit
8: 8-bit
7No
C074
Communication
parity selection
00: No parity
01: Even
02: Odd
00 No
C075
Communication stop
bit selection
1: 1-bit
2: 2-bit
1No
C076
Communication error
selection
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free-run stop
04: Deceleration stop
02 No
C077
Communication error
timeout
0.00 to 99.99 0.00 No s
4-102
4-140
C078
Communication wait
time
0. to 1000. 0. No ms
4-140
C079
Communication
method selection
00: ASCII
01: ModBus-RTU
01 No
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.