67
Special Settings and Communications Settings Section 4-8
Unit Number Setting: UNO (Unit Number)
The unit number setting display (UNO) will be displayed when the Down Key
( ) is pressed from the external tripping input display (TRG) for branch out-
put 4.
Baud Rate: BPS (Bits Per Second)
The baud rate setting display (BPS) will be displayed if the Down Key ( ) is
pressed from the unit number setting display (UNO).
u n
o
0
1
(Return to UNO display.)
23
4
°C
kh
V
A
s
1
23
4
°C
kh
V
A
s
1
23
4
°C
kh
V
A
s
1
Set the S8M's unit number when using 1:N communications with
the host computer. The unit number can be left at its default value
(0) when communicating 1:1 with the computer.
Press the Key to display the unit number setting.
The setting can be changed by pressing the and
Keys (see note).
Note If the or Key is pressed for more than 2 s, the
SV will change by 10s instead of 1s.
Switch to the
baud rate set-
ting.
When the Key is pressed, the setting will flash.
When the flashing stops, the new setting will be
saved and the S8M will return to UNO display.
If you want to confirm the new setting, press the
Key again from the UNO display.
If the Down Key ( ) is pressed from the UNO display, the display will switch to the baud
rate setting display (BPS).
The setting range is 0 to 31. The unit number can be
left at 0 when communicating 1:1 with the computer.
Change the SV with the and Keys.
The S8M will automatically return to the UNO dis-
play if no key is pressed within 3 s.
b p
s
23
4
°C
kh
V
A
s
1
This parameter sets the RS-232C port's baud rate to
4,800 bps or 9,600 bps.