3-34
Param-
eter
No.
MemoChan-
ges
during
opera-
tion
Default
setting
Set-
ting
range
DescriptionNameRegis-
ter No.
(Hex)
n149 0195 Pulse train
input scale
Set this parameter to the pulse train
input scale so that frequency refer-
ences can be executed by pulse
train input.
Set the maximum pulse train fre-
quency in 10-Hz increments based
on 10 Hz as 1.
Note This parameter is enabled
with n004 for frequency refer-
ence selection set to 5.
100 to
3,300
2,500 No
n150 0196 Multi-function
analog out-
put, pulse
train fre-
quency
selection.
Select the relationship between the
pulse train output frequency and out-
put frequency.
0: 1,440 Hz at max. frequency (A
proportional relationship is applied
to frequencies less than the maxi-
mum frequency)
1: 1x output frequency
6: 6x output frequency
12: 12x output frequency
24: 24x output frequency
36: 36x output frequency
Note This parameter is enabled
with n065 set to 1.
0, 1,
6, 12,
24, 36
0 No
n151 0197 RS-422/485
communica-
tions time-
over detec-
tion selection
The set value in the parameter
determines whether communications
time-over detection will be per-
formed with “CE” displayed if there
is an interval of more than 2 s
between normal communications
and how the detected communica-
tions time-over will be processed.
0: Detects time-over, fatal error, and
the Inverter coasts to a stop.
1: Detects time-over, detects fatal
error, and the Inverter decelerates
to a stop in deceleration time 1.
2: Detects time-over, detects fatal
error, and the Inverter decelerates
to a stop in deceleration time 2.
3: Detects time-over, detects nonfa-
tal error warning, and the Inverter
continues operating.
4: No time-over is detected.
0 to 4 0 No
List of Parameters Chapter 3