478
E5
@
K Digital Controller Read Protocol Appendix F
Receive Data Word Allocation (4th Operand of PMCR(260))
Read Level 1 Parameters 2 (Sequence No. 020 (Hex 0014))
Reads parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hystere-
sis (cooling), control period (heating), and control period (cooling)) from multiple units and stores the results in
the specified words.
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits Hex)
Number of units × 6 + 1
+1 1st unit
Alarm value 1 (4 digits BCD)
A999 to 9999
F indicates a negative value and A indi-
cates –1.
+2 1st unit
Alarm value 2 (4 digits BCD)
A999 to 9999
F indicates a negative value and A indi-
cates –1.
+3 1st unit
Alarm value 3 (4 digits BCD)
A999 to 9999
F indicates a negative value and A indi-
cates –1.
+4 1st unit
Proportional band
(4 digits BCD)
0001 to 9999
+5 1st unit
Integral time (4 digits BCD)
0000 to 3999
+6 1st unit
Derivative time (4 digits BCD)
0000 to 3999
+48
(max.)
8th unit
Derivative time (4 digits BCD)
0000 to 3999
Alarm value 1
Receive
data storage
words
Number of receive data words
+0
+1
+2
+3
+4
+5
+6
+43
+44
+45
+46
+47
+48
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
~ ~
Alarm value 2
Alarm value 3
Proportional band
Integral time
1st unit
8th unit (max.)
Derivative time
Derivative time