95
Response Format
@ RP
Unit no. FCS TerminatorHeader
code
Response
code
Program
1 byte
x 10
0
x 10
1
x 16
1
x 16
0
x 16
1
x 16
0
*s
Parameter Program (response): The program data will be as large as the memory size
regardless of the size of the program.
5-31 PROGRAM WRITE
Writes a machine language (octal) program into the PC program memory.
Command Format
@ WP
Unit no. FCS TerminatorHeader
code
Program (up to maximum
memory capacity)
1 byte
x 10
0
x 10
1
x 16
1
x 16
0
*s
Response Format
@ WP
Unit no. FCS TerminatorHeader
code
Response
code
x 10
0
x 10
1
x 16
1
x 16
0
*s
Parameter Program (response): The program data can be as large as the maximum
memory size.
5-32 I/O TABLE GENERATE
Regenerates the I/O table to match the actual I/O connected to the PC.
Command Format
@ MI
Unit no. FCS TerminatorHeader
code
*s
x 10
0
x 10
1
Response Format
@ MI
Unit no. FCS TerminatorHeader
code
Response
code
x 10
0
x 10
1
x 16
1
x 16
0
*s
5-33 I/O REGISTER
I/O REGISTER is used both to register memory area words or bits to be read and
to actually read the content of the words and bits that have been registered.
Caution This command is supported only by CPUs of version 1 or later or by Host Link
Units.
I/O REGISTER Section 5-33

Table of Contents

Other manuals for Omron SYSMAC CV1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CV1000 and is the answer not in the manual?

Omron SYSMAC CV1000 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CV1000
CategoryController
LanguageEnglish

Related product manuals