5 Start Up
I67E-EN V1000 Quick Start Guide 19
ENGLISH
For Auto-Tuning enter the Auto-Tuning menu and perform the steps shown in the figure
below. The number of name plate data to be entered depends on the selected type of Auto-
Tuning. This example shows Rotational Auto-Tuning.
If Auto-Tuning can not be performed for some reason (no-load operation impossible etc.),
then set up the maximum frequency and voltage in the E1- parameters and enter the
motor data manually into the E2- parameters.
NOTICE! The Safe Disable inputs must be closed during Auto-Tuning.
Enter the Auto-
Tuning Mode
Select the tuning
method
Set up all name
plate data
The tuning start
display appears
During the tuning the
DRV LED flashes
After successful tuning
“End” is displayed
Drive mode
display

Other manuals for Omron V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron V1000 and is the answer not in the manual?

Omron V1000 Specifications

General IconGeneral
Cooling MethodFan cooling
Enclosure RatingIP20
CommunicationModbus RTU
Output Power0.4-15kW
Output Frequency Range0 to 400 Hz
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
Supply Voltage200-240V AC (3-phase)

Related product manuals