152
0029H
Fault description
0(Not used)
1(Not used)
2 Input open phase (PF)
3 Output open phase (LF)
4-F (Not used)
002AH
Alarm description
0 Operation function stop (STP)
1 Sequence error (SER)
2 Simultaneous FWD/REV Run Commands (EF)
3 External Baseblock (BB)
4 Overtorque detection (OL3)
5 Cooling fan overheat (OH)
6 Main circuit overvoltage (OV)
7 Main circuit undervoltage (UV)
8 Cooling fan fault (FAN)
9 Communications fault (CE)
A Option card communications error (BUS)
B Undertorque (UL3)
C Inverter overheat alert (OH3)
D PID feedback loss (FBL)
E Emergency stop (STP)
F Communications waiting (CAL)
002BH
Sequence input status
0 Terminal S1 1: Closed 0: Open
1 Terminal S2 1: Closed 0: Open
2 Terminal S3 1: Closed 0: Open
3 Terminal S4 1: Closed 0: Open
4 Terminal S5 1: Closed 0: Open
5 Terminal S6 1: Closed 0: Open
6 Terminal S7 1: Closed 0: Open
7-F (Not used)
Register
No.
Bit Description