92
n065 Setting
Pulse train signal can be selected by setting in n150.
Note: Enabled only when n065 is set to 1 (pulse monitor output).
n065 Setting Description
0 Analog monitor output
1 Pulse monitor output
(Output frequency monitor)
n150 Setting Description
0 Output
frequency
monitor
1440 Hz/Max. frequency (n011)
1 1F: Output frequency × 1
6 6F: Output frequency × 6
12 12F: Output frequency × 12
24 24F: Output frequency × 24
36 36F: Output frequency × 36
40 Frequency
reference
monitor
1440 Hz/Max. frequency (n011)
41 1F: Output frequency × 1
42 6F: Output frequency × 6
43 12F: Output frequency × 12
44 24F: Output frequency × 24
45 36F: Output frequency × 36
50 Data Output
via Communi-
cations
0 to 14,400 Hz output (MEMO-
BUS register No.000AH) (1 Hz/
1)