96
The factory setting depends on the Inverter capacity (kVA).
* Reduction of the current is not necessary.
Voltage
Class (V)
Capacity
(kW)
Factory Setting Maximum
Continuous
Output
Current (A)
Reduced
Current
(A)
Continu-
ous Output
Current
(Reduction
Output
Current)
(A)
Setting Carrier
Frequency
(kHz)
FC =
14 kHz
200 V Sin-
gle-phase
or 3-phase
0.1 4 10 0.8
-
0.7 (88%)
0.25 4 10 1.6 1.4 (88%)
0.55 4 10 3.0 2.6 (87%)
1.1 4 10 5.0 4.3 (86%)
1.5 3 7.5 8.0 7.0 6.0 (75%)
2.2 3 7.5 11.0 10.0 8.6 (78%)
4.0 3 7.5 17.5 16.5 14.0 (80%)
5.5 3 7.5 25 23 18.0 (72%)
7.5 3 7.5 33 30 22.1 (67%)
400 V
3-phase
0.37 3 7.5 1.2 1.0 0.8 (67%)
0.55 3 7.5 1.8 1.6 1.28 (71%)
1.1 3 7.5 3.4 3.0 2.2 (65%)
1.5 3 7.5 4.8 4.0 3.2 (67%)
2.2 3 7.5 5.5 4.8 3.84 (70%)
3.0 3 7.5 7.2 6.3 4.9 (68%)
4.0 3 7.5 9.2 8.1 6.4 (74%)
5.5 3 7.5 14.8 * 12.0 (81%)
7.5 3 7.5 18 17 13.0 (72%)