FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 26 onicon.com
3.5.3 Temperature Sensor Connection (For Energy Version Only)
SIGNAL (+)
REFERENCE (-)
SHIELD
Supply Temperature Sensor
Temperature Sensor Connection (For Energy Version Only)
SIGNAL (+)
REFERENCE (-)
SHIELD
Return Temperature Sensor
BROWN
YELLOW
WHITE
GREEN
Supply Temperature Sensor
A
A
B
B
2W
4W
*Move Jumper J8 & J9 for 2W or 4W RTD
BROWN
YELLOW
WHITE
GREEN
Return Temperature Sensor
A
A
B
B
2W
4W
*Move Jumper J10 & J11 for 2W or 4W RTD
OR
1
0
1
0
1
0
NOTE:
Conrm the type of temperature sensor provided. The wiring on the left is for a TSP-RKP-XXXX and the wiring on
the right is for TSP-OFR-XXX which is the most common temperature sensor. Refer to the image above to identify
the provided temperature sensor.
RTD Sensor vs. ONICON Solid State Sensor