EasyManua.ls Logo

Onicon FT-3500 - Temperature Sensor Connection Wiring

Onicon FT-3500
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 26 onicon.com
3.5.3 Temperature Sensor Connection (For Energy Version Only)
SIGNAL (+)
REFERENCE (-)
SHIELD
Supply Temperature Sensor
Temperature Sensor Connection (For Energy Version Only)
SIGNAL (+)
REFERENCE (-)
SHIELD
Return Temperature Sensor
BROWN
YELLOW
WHITE
GREEN
Supply Temperature Sensor
A
A
B
B
2W
4W
*Move Jumper J8 & J9 for 2W or 4W RTD
BROWN
YELLOW
WHITE
GREEN
Return Temperature Sensor
A
A
B
B
2W
4W
*Move Jumper J10 & J11 for 2W or 4W RTD
OR
1
0
1
0
1
0
NOTE:
Conrm the type of temperature sensor provided. The wiring on the left is for a TSP-RKP-XXXX and the wiring on
the right is for TSP-OFR-XXX which is the most common temperature sensor. Refer to the image above to identify
the provided temperature sensor.
RTD Sensor vs. ONICON Solid State Sensor

Other manuals for Onicon FT-3500