3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 27 onicon.com
3.5.4 Network Communications Outputs
DO NOT USE
GND
(-)
(+)
BACnet MSTP or MODBUS RTU
Network Communications Outputs
RJ 45
BACnet /IP or MODBUS TCP/IP
1
0
1
0
1
0
End-of-Line Resistor (J7)
Left=Terminated
Right=Unterminated
Terminate if the meter is the LAST
device on the network.
NOTE: Do not connect shield to ground (GND)