FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 55 onicon.com
5.5 TROUBLESHOOTING GUIDE
NOTE: Also refer to the START-UP AND COMMISSIONING GUIDE located on page 46/47.
REPORTED PROBLEM POSSIBLE SOLUTIONS
No signal • Verify that the meter is properly inserted into the pipe.
• Verify that the remote sensor ow arrow points in the direction of ow in the pipe.
• Verify 24 V supply voltage.
• Verify correct wiring to control system (see wiring diagram).
• Verify that there is ow in the pipe.
• Verify that the meter earth cable is connected to earth.
• Low conductivity water (≤ 20 µsiemens) may activate the empty pipe detector and/
or increase the potential for electrical noise problems.
Reading is too high or low • Verify pipe size. Contact ONICON if pipe size is dierent from calibration tag.
• Verify that the meter is properly inserted into the pipe.
• Verify that the remote sensor ow arrow points in the direction of ow in the pipe.
• Verify correct wiring to control system (see wiring diagram).
• Conrm that the output signals are consistent with each other (frequency vs.
analog, etc).
• Conrm that the control system is programmed for correct ow range or scale
factor.
• Verify that the meter earth cable is connected to earth. A poor earth connection
can lead to excessive noise that can aect the ow reading.
Analog signal seems
high or low and does not
correspond to frequency
output
• Verify Analog Out Max and Flow at MaxFreq
• Check for ground loop or oset voltage:
• Disconnect analog signal input from control system and measure analog output
directly from the ow meter. Reconnect signal input to control system and
measure the analog signals again. Any dierence between these readings indicates
a potential ground loop or oset voltage. Please contact ONICON for further
assistance.
Control system displays
ow rate, but no ow rate
is indicated on the local
display module or Btu
meter
• Verify that all wires from the ow meter are connected to the display module or Btu
meter.
• The frequency output wires (green and yellow) must be connected for any ONICON
display or Btu meter.