EasyManua.ls Logo

Onicon FT-3500 - FT-3500 Troubleshooting Guide

Onicon FT-3500
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 55 onicon.com
5.5 TROUBLESHOOTING GUIDE
NOTE: Also refer to the START-UP AND COMMISSIONING GUIDE located on page 46/47.
REPORTED PROBLEM POSSIBLE SOLUTIONS
No signal Verify that the meter is properly inserted into the pipe.
Verify that the remote sensor ow arrow points in the direction of ow in the pipe.
Verify 24 V supply voltage.
Verify correct wiring to control system (see wiring diagram).
Verify that there is ow in the pipe.
Verify that the meter earth cable is connected to earth.
Low conductivity water (≤ 20 µsiemens) may activate the empty pipe detector and/
or increase the potential for electrical noise problems.
Reading is too high or low Verify pipe size. Contact ONICON if pipe size is dierent from calibration tag.
Verify that the meter is properly inserted into the pipe.
Verify that the remote sensor ow arrow points in the direction of ow in the pipe.
Verify correct wiring to control system (see wiring diagram).
Conrm that the output signals are consistent with each other (frequency vs.
analog, etc).
Conrm that the control system is programmed for correct ow range or scale
factor.
Verify that the meter earth cable is connected to earth. A poor earth connection
can lead to excessive noise that can aect the ow reading.
Analog signal seems
high or low and does not
correspond to frequency
output
Verify Analog Out Max and Flow at MaxFreq
Check for ground loop or oset voltage:
Disconnect analog signal input from control system and measure analog output
directly from the ow meter. Reconnect signal input to control system and
measure the analog signals again. Any dierence between these readings indicates
a potential ground loop or oset voltage. Please contact ONICON for further
assistance.
Control system displays
ow rate, but no ow rate
is indicated on the local
display module or Btu
meter
Verify that all wires from the ow meter are connected to the display module or Btu
meter.
The frequency output wires (green and yellow) must be connected for any ONICON
display or Btu meter.

Other manuals for Onicon FT-3500

Related product manuals