FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 62 onicon.com
8.0 WARNINGS
ALERT POTENTIAL ISSUE POSSIBLE SOLUTION
“Warn Reverse Flow” Flow is owing contrary to ow direction
indicator on meter stem
Not an actual issue present. The warning is present
as a message when the ow is going in the opposite
direction for bidirectional meters.
“Warn Low Flow” Flow is below low ow warning threshold (0.25
ft/sec), or low limit specied over BACnet
• Verify poper meter installation
• Ensure water is owing in pipe.
• Check low limit of Volume Rate BACnet object if
applicable.
“Warn High Flow” Flow is above high ow warning threshold (19
ft/sec)
Reduce ow in pipe
“Warn AOUT 1 Low Flow” Analog Out ow is below low ow threshold
(0.25 ft/sec) - port 1
• Verify proper meter installation
• Ensure water is owing in pipe.
• Check cong in Analog Outputs screen, Pipe
Cong Settings screen.
“Warn AOUT 1 High Flow” Analog Out ow is above high ow warning
threshold (19 ft/sec) - port 1
• Reduce ow in pipe.
• Check cong in Analog Outputs screen, Pipe
Cong Settings screen.
“Warn AOUT 2 Low Flow” Analog Out ow is below low ow threshold
(0.25 ft/sec) - port 2
• Verify proper meter installation
• Ensure water is owing in pipe.
• Check cong in Analog Outputs screen, Pipe
Cong Settings screen.
“Warn AOUT 2 High Flow” Analog Out ow is above high ow warning
threshold (19 ft/sec) - port 2
• Reduce ow in pipe.
• Check cong in Analog Outputs screen, Pipe
Cong Settings screen.
“Warn AOUT 1 HW Failure” Analog output controller hardware reports
temperature exeeds max threshold (142 C) -
Analog Out port 1
Verify meter operating environment temperature is
within listed specication (-20°F to 150°F). If problem
persists contact ONICON support.
“Warn AOUT 1 Open Circuit or Bad
Voltage”
Analog output controller hardware reports open
circuit or bad voltage - Analog Out port 1
• Check Power to the transmitter is ##
• Check Analog Output 1 connection in the
transmitter.
• Verify Analog Output 1 wiring to BAS to ensure
correct no wires are damaged or crossed.
• Verify conguraiton of Analog Input at BAS.
• If problem persists, contact ONICON support
“Warn AOUT 1 Communications Fail” Analog output controller hardware reports
communications failure - Analog Out port 1
Contact ONICON. RMA needed
“Warn AOUT 1 Timeout” Analog output controller hardware reports
execution timeout - Analog Out port 1
Contact ONICON. RMA needed
“Warn AOUT 2 HW Failure” Analog output controller hardware reports
temperature over max threshold (142C) - Analog
Out port 2
Contact ONICON. RMA needed
“Warn AOUT 2 Open Circuit or Bad
Voltage”
Analog output controller hardware reports open
circuit or bad voltage - Analog Out port 2
• Check Power to the transmitter is ##
• Check Analog Output connection in the
transmitter.
• Verify Analog Output wiring to BAS to ensure
correct no wires are damaged or crossed.
• Verify conguraiton of Analog Input at BAS.
• If problem persists, contact ONICON support.