8.0 WARNINGS
ALERT POTENTIAL ISSUE POSSIBLE SOLUTION
“Warn Reverse Flow” Flow is owing contrary to ow direction
indicator on meter stem
Not an actual issue present. The warning is present
as a message when the ow is going in the opposite
direction for bidirectional meters.
“Warn Low Flow” Flow is below low ow warning threshold (0.25
ft/sec), or low limit specied over BACnet
Verify poper meter installation
Ensure water is owing in pipe.
Check low limit of Volume Rate BACnet object if
applicable.
“Warn High Flow” Flow is above high ow warning threshold (19
ft/sec)
Reduce ow in pipe
“Warn AOUT 1 Low Flow” Analog Out ow is below low ow threshold
(0.25 ft/sec) - port 1
Verify proper meter installation
Ensure water is owing in pipe.
Check cong in Analog Outputs screen, Pipe
Cong Settings screen.
“Warn AOUT 1 High Flow” Analog Out ow is above high ow warning
threshold (19 ft/sec) - port 1
Reduce ow in pipe.
Check cong in Analog Outputs screen, Pipe
Cong Settings screen.
“Warn AOUT 2 Low Flow” Analog Out ow is below low ow threshold
(0.25 ft/sec) - port 2
Verify proper meter installation
Ensure water is owing in pipe.
Check cong in Analog Outputs screen, Pipe
Cong Settings screen.
“Warn AOUT 2 High Flow” Analog Out ow is above high ow warning
threshold (19 ft/sec) - port 2
Reduce ow in pipe.
Check cong in Analog Outputs screen, Pipe
Cong Settings screen.
“Warn AOUT 1 HW Failure” Analog output controller hardware reports
temperature exeeds max threshold (142 C) -
Analog Out port 1
Verify meter operating environment temperature is
within listed specication (-20°F to 150°F). If problem
persists contact ONICON support.
“Warn AOUT 1 Open Circuit or Bad
Voltage”
Analog output controller hardware reports open
circuit or bad voltage - Analog Out port 1
Check Power to the transmitter is ##
Check Analog Output 1 connection in the
transmitter.
Verify Analog Output 1 wiring to BAS to ensure
correct no wires are damaged or crossed.
Verify conguraiton of Analog Input at BAS.
If problem persists, contact ONICON support
“Warn AOUT 1 Communications Fail” Analog output controller hardware reports
communications failure - Analog Out port 1
Contact ONICON. RMA needed
“Warn AOUT 1 Timeout” Analog output controller hardware reports
execution timeout - Analog Out port 1
Contact ONICON. RMA needed
“Warn AOUT 2 HW Failure” Analog output controller hardware reports
temperature over max threshold (142C) - Analog
Out port 2
Contact ONICON. RMA needed
“Warn AOUT 2 Open Circuit or Bad
Voltage”
Analog output controller hardware reports open
circuit or bad voltage - Analog Out port 2
Check Power to the transmitter is ##
Check Analog Output connection in the
transmitter.
Verify Analog Output wiring to BAS to ensure
correct no wires are damaged or crossed.
Verify conguraiton of Analog Input at BAS.
If problem persists, contact ONICON support.