FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 54 onicon.com
Objects List
Object Identier Function UNITS
BI 0 Mode Indication
Indicates current operating mode (Mode 1 or Mode 2) for
Channel 1. Mode 1 = Forward Cooling / Mode 2 = Reverse
Heating
BINARY INPUT
Objects List
Object Identier Object Name Description
MSV 0 Errors
18 states that indicate hardware or functional failures
1. Normal
2. EEPROMFail
3. I2CFail
4. VelTblCrrpt
5. PipCfgMssng
6. GrnTtlCrrpt
7. YrTtlCrrpt
8. ElecDiOOR
9. Elec0 D/C
10. Elec1 D/C
11. ElecBckwrds
12. CoilOpen
13. CoilShort
14. CoilOOR
15. EmptyPipe
16. BrdTempFail
17. 3.3VRailLow
18. RtcFail
MULIT-STATE VALUE