FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 53 onicon.com
Objects List
Object Identier Function UNITS
Analog Input 1 Energy Rate Btu/Hr, Kw, or Tons
Analog Input 2 Volume Rate L/Sec, L/Min, L/Hr, M
3
/Hr, GPM, CFS, or CFM
Analog Input 3 Supply Temperature °C or °F
Analog Input 4 Return Temperature °C or °F
Analog Input 5 Delta Temperature °C or °F
ANALOG INPUT(S)
Objects List
Object Identier Function UNITS
Analog Value 1 Mode 1 Energy Total Btu, TonHrs, or kWHrs
Analog Value 2 Mode 1 Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 3 Mode 2 Energy Total Btu, TonHrs, or kWHrs
Analog Value 4 Mode 2 Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 5 Aux Input 1 Total Counts
Analog Value 6 Aux Input 2 Total Counts
Analog Value 7 Aux Input 3 Total Counts
Analog Value 8 Total Run Hr Hr
Analog Value 9 Run Hr Mode 1 Hr
Analog Value 10 Run Hr Mode 2 Hr
Analog Value 11 Mode 1 YTD Energy Total Btu, TonHrs, or kWHrs
Analog Value 12 Mode 1 PrevYr Energy Total Btu, TonHrs, or kWHrs
Analog Value 13 Mode 1 User Energy Total Btu, TonHrs, or kWHrs
Analog Value 14 Mode 1 Yesterday Energy Total Btu, TonHrs, or kWHrs
Analog Value 15 Mode 1 Last 30 Days Energy Total Btu, TonHrs, or kWHrs
Analog Value 16 Mode 1 YTD Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 17 Mode 1 PrevYr Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 18 Mode 1 User Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 19 Mode 1 Yesterday Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 20 Mode 1 Last 30 Days Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 21 Mode 2 YTD Energy Total Btu, TonHrs, or kWHrs
Analog Value 22 Mode 2 PrevYr Energy Total Btu, TonHrs, or kWHrs
Analog Value 23 Mode 2 User Energy Total Btu, TonHrs, or kWHrs
Analog Value 24 Mode 2 Yesterday Energy Total Btu, TonHrs, or kWHrs
Analog Value 25 Mode 2 Last 30 Days Energy Total Btu, TonHrs, or kWHrs
Analog Value 26 Mode 2 YTD Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 27 Mode 2 PrevYr Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 28 Mode 2 User Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 29 Mode 2 Yesterday Volume Total Liters, M
3
, Gallons, or Ft
3
Analog Value 30 Mode 2 Last 30 Days Volume Total Liters, M
3
, Gallons, or Ft
3
ANALOG VALUE(S)
Fault = Alarm (Empty pipe, Electrode Disconnect, etc.)
Oimit = Warn Low Flow

Other manuals for Onicon FT-3500