FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 52 onicon.com
Device
Required Properties:
Object Identier (W), Object Name (W), APDU Timeout (W), Number of APDU Retries (W)
Optional Properties Supported:
Description C, Local Date (W), Local Time (W), UTC Oset (W), Daylight Savings Status (W),
Max Master (W), Max Info Frames (W)
File
Required Properties:
Object Name (W)
Optional Properties Supported:
Description (W)
Multi-state Value
Required Properties:
Object Name (W)
Optional Properties Supported:
Description (W), State Text
Notication Class
Required Properties:
Object Name, (W) Ack Required (W), Recipient List (W)
Optional Properties Supported:
Description (W)
Large Analog Value
Required Properties:
Object Name (W)
Present Value (“user dened” and “aux” pulse total AV objects are resettable by writing 0)
Optional Properties Supported:
Description (W), Priority Array, COV Increment (W), Relinquish Default
BACnet Data Link Layer Options:
BACnet IP, (Annex J)
MS/TP master (Clause 9)
Master Slave
Non-isolated transceiver Isolated transceiver
Local 47K ohms bias resistors None Other: _________________
Transceiver unit loading: 1 ½ ¼
Data rates: 9600 19200 38400 57600 76800 115200
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain
other devices.) Yes No
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ISO 10646 (UTF-8) IBM™/Microsoft™ DBCS ISO 8859-1
ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208