BACnet Protocol Implementation Conformance Statement
Date: 01/03/2023
Vendor Name: ONICON Inc.
Product Name: FT-3500
Product Model Number: FT-3500-1 and FT-3500-2
Application Software Version: 2.6.0
Firmware Revision: 1.8.0
BACnet Protocol Revision: 16
BACnet Standardized Device Proles Supported (Annex L):
BACnet Application Specic Controller (B-ASC)
BACnet Interoperability Building Blocks Supported (Annex K): DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B,
DS-COV-B, AE-N-I-B, AE-ACK-B, AE-INFO-B, AE-CRL-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-TS-B,
DM-UTC-B, DM-RD-B
Segmentation Capability:
Able to transmit segmented messages Window Size __________________________
Able to receive segmented messages Window Size __________________________
Standard Object Types Supported:
The properties below are only those whose presence or writability exceed the minimum requirements of the published
ASHRAE BACnet Standard. Properties denoted with (W) are those that are not required to be writable but which have
had the ability enabled. All other properties not shown that are required to be present, readable, and/or writable are in
accordance with the Standard.
Dynamic object creation and deletion is not supported for any object type.
Analog Input
Required Properties:
Object Name (W)
Present Value (commandable when “Out of Service” is True)
Optional Properties Supported:
Description (W), COV Increment (W), Time Delay (W), Notication Class, High Limit (W), Low Limit (W),
Deadband (W), Limit Enable (W), Event Enable (W), Acked Transition Bits, Notify Type, Event Time Stamps, Event
Text Messages, Event Algorithm Inhibit Ref, Event Algorithm Inhibit
Analog Value
Required Properties:
Object Name (W)
Present Value (“user dened” and “aux” pulse total AV objects are resettable by writing 0)
Optional Properties Supported:
Description (W), Priority Array, COV Increment (W), Relinquish Default
Binary Input
Required Properties:
Object Name
Optional Properties Supported:
Description (W), Inactive Text, Active Text
Binary Value
Required Properties:
Object Name (W), Present Value (W)
Optional Properties Supported:
Description (W), Inactive Text, Active Text, Priority Array (W), Relinquish Default (W)