FT
-
3500 ELECTROMAGNETIC FLOW METER
ONICON Incorporated 727.447.6140 Page 50 onicon.com
i
IMPORTANT NOTE FOR BACnet MS/TP CONNECTIONS
If the meter is not connected to an active network the following electrical testing can be performed with a
multimeter. If the readings are outside for the normal ranges listed below, please refer to manual for common
issues.
I. Check Resistance (set multimeter to Ohms)
Shield
Earth Ground
Normal reading: 0 Ohms
II. Check DC Voltage (set multimeter to DC)
A-
B+
Normal reading: 0.2 VDC
III. Check DC Voltage (set multimeter to DC)
Earth Ground
B+
Normal reading: 2.0 - 2.5 VDC
IV. Check DC Voltage (set multimeter to DC)
Earth Ground
A-
Normal reading: 2.0 - 2.5 VDC
V. Check DC Voltage (set multimeter to DC)
B+
Earth Ground
Normal reading: Less than 2.0 VDC
VI. Check DC Voltage (set multimeter to DC)
A-
Earth Ground
Normal reading: Less than 2.0 VDC