Connection
−29−
WNG output
When a warning is generated, the WNG output is turned ON. The motor will continue to operate.
The WNG output will be turned OFF automatically once the cause of the warning is removed.
WNG output
ON
OFF
10 ms or less
10 ms or less
Warning Generate
Warning list
Warning type Cause Remedial action
Main circuit overheat
The temperature inside the driver exceeded the
overheat warning level.
Reconsider the ventilation condition in the
enclosure.
Undervoltage
*
The main power supply voltage dropped by
approximately 10% or more from the rated voltage.
Check the input voltage of the main power
supply.
Check the wiring of the power supply cable.
Overload
*
The load torque of the motor exceeded the overload
warning level.
Decrease the load.
Reconsider the operating condition such as
acceleration time and deceleration time.
Operation prohibited
When moved from the test mode to other mode
using the
MEXE02
or
OPX-2A
, the FWD input or
REV input was being ON.
When the assignment of the input terminal was
changed using the
MEXE02
or
OPX-2A
, the
assigned terminal was ON.
Turn the input signal OFF.
*
The detection level can be changed using the
MEXE02
or
OPX-2A
.
Using a controller with a built-in clamp diode
If a controller with a built-in clamp diode is used, a leakage
path may form and cause the motor to operate even when the
controller power is o, as long as the driver power is on. Since
the power capacity of the controller is dierent from that of the
driver, the motor may operate when the controller and driver
powers are turned on or o simultaneously.
When powering down, turn o the driver power rst, followed
by the controller power, and when powering up, turn on the
controller power rst, followed by the driver power.
External control
equipment
Driver
1 to 4, 9, 10
5
VCC +15 V
0 V
0 V
7.4 Connecting the communication cable
Connect a cable of the
MEXE02
or
OPX-2A
to the communication
connector (CN7).
Refer to the USER MANUAL (RS-485 Communication Mode) for
connection of RS-485 communication.
MEXE02 or OPX-2A
cable