Setting contents of MEXE02
−62−
•
Timing chart in the 2-wire mode
FWD input
OFF
ON
OFF
ON
ON
REV input
OP-MODE input
Instantaneous stop
Rotation direction switching/Stop mode selection
Instantaneous
stop
Motor operation
CW
CCW
Deceleration stop
Deceleration stop
Note
•
To surely recognize the input signal, ensure the ON time and OFF time of each input signal for at least
10ms.
•
When switching the FWD input and REV input, provide an interval of at least 10 ms.
•
Timing chart in the 3-wire mode
Motor operation
ART/STOP input
OFF
ON
OFF
ON
ON
RUN/BRAKE input
FWD/REV input
CW/CCW operation
Instantaneous
stop
Stop mode selection
Instantaneous
stop∗
Deceleration
stop
CW
CCW
∗*
If the rotation direction is changed during operation, the rotation direction will be changed after instantaneous stop.
Note
To surely recognize the input signal, ensure the ON time and OFF time of each input signal for at least 10
ms.
11.8 Communication
A: Update immediately, D: Update after turning on the power again
Parameter name Description Setting range Factory setting Update
Communication
timeout
Sets the condition in which a communication
timeout occurs in RS-485 communication.
0 to 10000 [ms]
(0: Not monitored)
0
A
Communication error
alarm
Sets the condition in which a RS-485 communication
error alarm is generated. A communication
error alarm will be generated after a RS-485
communication error has occurred by the number of
times set here.
1 to 10 [times] 3
Communication
parity
Sets the parity of RS-485 communication (Modbus
protocol).
None
Even number
Odd number
Even number
DCommunication stop
bit
Sets the stop bit for RS-485 communication (Modbus
protocol).
1 bit
2 bits
1 bit
Transmission waiting
time
Sets the transmission waiting time of RS-485
communication (Modbus protocol).
0.0 to 1000.0 [ms] 10.0