EasyManua.ls Logo

Pacific Power Source MS SERIES - Table 3.1 Environmental Survey Checklist

Default Icon
130 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 3 INSTALLATION
Pacific Power Source ©2013 3-3 Document # 126050-10 Rev E
CHECK AT RIGHT WHEN CONFIRMED
1.
Ambient temperature between 0-40 degrees Centigrade.
2.
Cooling and air exchange rates in the room adequate to
support the heat load.
3.
A minimum of 12" above the Cabinet for exhaust.
4.
Unrestricted air intake at the lower front and rear of the
cabinet. (Exception: Forced air intake from raised floor
installations requires sealing off of the lower front and rear
areas. Consult factory.)
5.
A minimum of 24" in front of the Cabinet for service.
6.
Altitude of installation does not exceed 6500 feet. Altitudes in
excess of 6500 feet require the derating of maximum operating
levels.
7.
Relative humidity does not exceed 80% (95% with conformal
coat PCB option) non-condensing. It is suggested that
equipment not be located directly under cooling equipment due
to the danger of condensing vapor.
TABLE 3.1 ENVIRONMENTAL SURVEY CHECKLIST

Table of Contents

Related product manuals