5.2 Current Range
5.2.1 Current Output Range: 0 to +20 mA (0.64 μA, 1/31,250)
Output range: 0 to +20 mA
Digital input
value (K)
Analog output
value (V)
+31,250 +20
+25,000 +16
+18,750 +12
+12,500 +8
+6,250 +4
0 0
When exceeding the rated
range
Digital input
value
Analog output
value
+32,500 or
more
Output at
20.8 mA
-1,250 or less Output at -0.8
mA
5.2.2 Current Output Range: +4 to +20 mA (0.64 μA, 1/25,000)
Output range: 0 to +20 mA
Digital input
value (K)
Analog output
value (V)
+25,000 +20
+18,750 +16
+12,500 +12
+6,250 +8
0 +4
When exceeding the rated
range
Digital input
value
Analog output
value
+26,250 or
more
Output at
20.8 mA
-1,250 or less Output at +3.2
mA