42
No.
Function
name
Changes
during RUN
Setting range Unit
Initial
value
P034
Reverse
Run Lock
-
0: Forward/Reverse run enabled
1: Reverse run disabled
- 0
P035
Starting
Frequency
○ 0.2 to 60.0 0.1[Hz] 0.2
P036 Stop Mode -
0: Deceleration stop
1: Coast-to-stop
- 0
P037
Stop
Frequency
○ 0.2 to 60.0 0.1[Hz] 0.2
P038
DC Braking
Time
○ 0.0 to 120.0
0.1[sec]
0.0
P039
DC Braking
Level
○ 0 to 100 1[%] 0
P040
Stop
Frequency
during
Forward /
Reverse
Run
○ 0.2 to 60.0 0.1[Hz] 0.2
P041
DC Braking
Time durig
Forward /
Reverse
Run
○ 0.0 to 120.0
0.1[sec]
0.0
P042
DC Braking
Level
during
Forward/
Reverse
Run
○ 0 to 100 1[%] 0
P043
DC Braking
Time during
Startup
○ 0.0 to 120.0
0.1[sec]
0.0
P044
DC Braking
Level
during
Startup
○ 0 to 100 1[%] 0
P045
Lower
Frequency
Limit
○ 0.2 to 400.0 0.1[Hz] 0.2
P046
Upper
Frequency
Limit
○ 0.2 to 400.0 0.1[Hz] 400.0
P047
Zero Dead
Stop
Function
Selection
- 0.0 · 0.2 to 400.0 0.1[Hz] 0.2
P048
1st Skip
Frequency
○ 0.0 · 0.2 to 400.0 0.1[Hz] 0.0
P049
2nd Skip
Frequency
○ 0.0 · 0.2 to 400.0 0.1[Hz] 0.0