1.5 CN-CNT communication error handling Control (Indoor Control)
Starng Condions:
1. When Duty Rotaon flag = ON
2. When indoor unit has not received CN-CNT signal from wired remote control for 3 min (counted by
a mer, this mer is reset each me when a CN-CNT signal is received) connuously.
Control content:
When both starng condions 1 and 2 are fulfilled:
1. Turn off indoor unit.
2. Set Duty Rotaon flag = OFF.
When starng condion 2 is fulfilled (regardless of starng condion 1 fulfilled or not):
1. Set Seng change thro’ WLAN Flag = Enable (allow wifi app to change seng)
** Note:
1. No cancel condions because when CN-CNT signal is received again from wired remote control, it
will overwrite the previous seng.
2. The mer in this control is same as the mer for wired remote control prohibion).