103
Indoor funconalies during Duty Rotaon
Illustrated below are the unit response on different cases encountered during Duty Rotaon as a result combined
acon from indoor CN-CNT communicaon error handling control and remote controller CN-CNT protocol.
A) During Duty Rotaon = OFF
B) During Duty Rotaon = ON
C) During Duty Rotaon = ON, CN-CNT A is malfunoned
1. CN-CNT Signal to A and B: OFF
2. Seng change through WRC (CN-RMT signal) Flag
for
A and B: Enabled
3. Seng change through WLAN Flag for
A and B: Enabled
4. Operaon ON/OFF for A and B: By CN-RMT Seng
5. Rotaon interval: Seng value
6. Duty rotaon flag for A and B: OFF
change signal
1. CN-CNT Signal to A and B: ON
2. Seng change through WRC (CN-RMT signal) Flag
for
A and B: Disabled by CN-CNT signal
3. Seng change through WLAN Flag for
A and B: Disabled by CN-CNT signal
4. Operaon ON/OFF for A and B: By rotaon interval
5. Rotaon interval: Seng value
6. Duty rotaon flag for A and B: ON
change signal
No wifi seng
change signal
1. CN-CNT Signal to A: OFF (Malfunconed), B: ON
2. Seng change through WRC (CN-RMT signal) Flag for
A: Enabled aer 3min no CN-CNT A signal, B: Disabled
3. Seng change through WLAN Flag for
A: Enabled aer 3min no CN-CNT A signal, B: Disabled
4. Operaon ON/OFF for
A: OFF aer 3mins no CN-CNT A signal unl recovery
B: ON by CN-CNT B signal after 1min no CN-CNT A signal
5. Rotaon interval: Aer 1min no CN-CNT A signal, set to
zero unl recovery
6. Duty rotaon flag for
A: OFF aer 3min no CN-CNT A signal unl recovery, B:
ON
No wifi seng
change signal