D) During Duty Rotaon = ON, CN-CNT B is malfunoned
E) During Duty Rotaon = ON, both CN-CNT A and B are malfunoned
Note:
1) WRC = Wired Remote Control
2) The above cases assume that users do not change Duty Rotaon seng at any me.
3) Aer both CN-CNTs are recovered from Case C, D, E, return to Case B.
4) If only CN-CNT A or CN-CNT B is recovered from Case E, return to Case D or Case C respecvely.
5) For running unit B in Case C and unit A in Case D, running operaon will follow seng set when duty
rotaon is started. To change seng through WRC (CN-RMT signal) or Wi-Fi, users need to turn off Duty
rotaon mode first in WRC. Aer turned off, Duty rotaon mode cannot be turned on again if the
malfunconed CN-CNT is not repaired.
6) If WRC B is not connected to Sub unit (B), seng change through WRC (CN-RMT signal) is not possible for
unit B.
Main unit (A)
Sub unit (B)
WRC A
WRC B
CN-RMT A
CN-RMT B
CN-CNT
CN-CNT B
Wifi seng
change signal
1. CN-CNT Signal to A: ON, B: OFF (Malfunconed)
2. Seng change through WRC (CN-RMT signal) Flag for
A: Disabled, B: Enabled aer 3min no CN-CNT B signal
3. Seng change through WLAN Flag for
A: Disabled, B: Enabled aer 3min no CN-CNT B signal
4. Indoor operaon for
A: ON, B: OFF aer 3min no CN-CNT B signal unl recovery
5. Rotaon interval: Aer 1min no CN-CNT A signal, set to
zero unl recovery
6. Duty rotaon flag for
A: ON, B: OFF aer 3min no CN-CNT B signal unl recovery
No wifi seng
change signal
Main unit (A)
Sub unit (B)
WRC A
WRC B
CN-RMT A
CN-RMT B
CN-CNT A
CN-CNT B
Wifi seng
change signal
Wifi seng
change signal
1. CN-CNT Signal to A and B: OFF (Malfunconed)
2. Seng change through WRC (CN-RMT signal) Flag for
A and B: Enabled aer 3min no CN-CNT A&B signal
3. Seng change through WLAN Flag for
A and B: Enabled aer 3min no CN-CNT A&B signal
4. Indoor operaon for
A and B: OFF aer 3min no CN-CNT A&B signal
5. Rotaon interval: Aer 1min no CN-CNT A/B signal, set to
zero unl CN-CNT A/B recovers
6. Duty rotaon flag for
A: OFF aer 3mins no CN-CNT A signal unl recovery
B: OFF aer 3mins no CN-CNT B signal unl recovery