MEW01622 Rev: - EBL128 Planning Instructions V2.0.x
108
than for a fire alarm type B. The alarm receiver can take different
actions depending on if it is a fire alarm type A or B.
13.14.1 Fire alarm type B
The output shall be programmed (via EBLWin) as type "Routing
equipment" and have the trigger condition "One detector alarm".
The output will be activated for fire alarm from one analog
addressable smoke, heat or multi
109
detector only.
13.14.2 Fire alarm type A
The output shall be programmed (via EBLWin) as type "Routing
equipment" and have the trigger condition "Multiple detector
alarm".
The output will be activated for fire alarm from:
Two or more analog addressable smoke, heat or multi
detectors.
Any manual call point
Any zone line input
Any programmable input with the trigger condition "General
Fire"
13.15 Disable zones, alarm points, outputs, etc.
Temporary disablements are made via the menu H2 sub menus. For
more information see the EBL128 Operating Instructions
(MEW01623), chapter "Disable or re-enable (H2)".
Regular disablements are made via time channels, see chapter "Time
channels", page 142.
When alarm reset method "Single with automatic disablement" is
selected via the EBLWin "System Properties", the function will be as
follows:
If an alarm point or zone is in alarm state when being reset it will not
only be reset but also disabled. It has to be re-enabled (via menu
H2/B6) the same way as if it was disabled via menu H2/B2.
Disabled alarm points and outputs are indicated by LED Fault /
Disablements "General disablements" on the c.i.e. front and are listed
in menu H4/U1-U2.
Enhanced Disablement (Default) = Fire alarm, pre-warning and fault
signal cannot be activated by the disabled alarm point/zone. If only
fire alarm and pre-warning shall be disabled, "Enhanced Disablement"
109
NOTE! A multi detector can have one presentation number (Zone-
Address) or two presentation numbers depending on how it is programmed
via EBLWin. One presentation number = one detector and two presentation
numbers = two detectors regarding fire alarm types A and B.