control expression.
Reset has to be performed via menu H9/C3.
11.3.3 Reset interlocking output (H9/C3)
Activated interlocking outputs are listed here. Use "↑" "↓" to scroll
between the "Interlocking Combinations" (Area / Point).
Interlocking output activated via its control expression and latching
output selected: The output has to be reset via this menu.
Interlocking output activated via its control expression and latching
output not selected: The output can be reset via this menu.
Interlocking output activated via menu H9/C2: The output has to be
reset via this menu.
11.3.4 Disable interlocking output (H9/C4)
Interlocking outputs (i.e. Output Type = Interlocking) can be disabled
via menu H9/C4. A disabled output will stay in (or return to) the
normal condition for the output respectively. The "Interlocking
Combination" (i.e. Area / Point) is to be entered to disable the output.
All interlocking outputs can be disabled collectively via menu H2/B4.
11.3.5 Re-enable interlocking output (H9/C5)
Interlocking outputs (i.e. Output Type = Interlocking) can be re-
enabled via menu H9/C5.
Disabled interlocking outputs are listed in menu H9/C5. Use "↑" "↓"
to scroll between the "Interlocking Combinations" (i.e. Area / Point)
or type it via the key-pad.
All interlocking outputs, disabled via menu H2/B4, can be re-enabled
via menu H2/B8.
11.4 Interlocking control expressions
A programmable output control expression can contain "interlocking"
trigger conditions ("Functions") numbers 14-17 (see chapter "Control
expression", page 78), i.e. one or more outputs can be activated when
one or more interlocking inputs are activated.