Relay contacts: max. 2 A @ 30 V DC / 125 V AC (60W).
Connections and more information, see drawings 128-21 & -26.
9.6 The 3364 unit outputs VO0, VO1 & VO2
Each 3364 unit has two programmable, supervised (monitored)
66
voltage outputs:
VO0 Supervised (monitored) voltage output, 24V DC, max. 1A
VO1 Supervised (monitored) voltage output, 24V DC, max. 1A
69
VO2 is a voltage output, 24V DC, max. 1A
69
, intended for fire door
closing. Normally high. For more information see the
Technical Description MEW00529.
24 V DC required from an external power supply unit (e.g. 3366).
Connections, see drawing 128-21 & -28.
9.7 The 3377 / 4477 unit output (siren)
Each unit has one programmable output:
Output Siren, with three priority levels and three sound types.
Connections and more information, see drawing 128-21.
9.8 The 3378 unit output (sounder)
Each 3378 unit has one programmable output:
Output Sounder, with three priority levels and three sound types.
Connections and more information, see drawing 128-21.
9.9 The 3379 unit output (sounder)
Each 3379 unit has one programmable output:
Output Sounder, with three priority levels and three sound types.
Connections and more information, see drawing 128-21.
9.10 The 4380 unit output (beacon)
Each 4380 unit has one programmable output:
Output Beacon
Connections and more information, see drawing 128-21.
9.11 The 4383 unit output (Light indicator)
Each 4383 unit has one programmable output:
Output Light indicator
Connections and more information, see drawing 128-21.
Cont. 1 A, during 10 ms 1.4 A.