25
5.1 Expansion board address setting
The expansion board address is set via jumpers on the expansion
board respectively.
Figure 5. Expansion boards 4580 - 4583. Jumpers for
expansion board address setting.
5.2 8 zones expansion board 4580
Up to four 4580 boards can be used.
Each board has to be programmed via EBLWin regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5 above.)
The 4580 board has eight conventional zone line inputs (0-7) intended
for conventional detectors. In the last alarm point on each zone line,
an end-of-line device has to be connected, depending on the selected
"Type of zone line input", see below.
Connections to "J1:1-16" and "J2" according to drawing 128-30.
Each zone line input has to be programmed via EBLWin regarding:
Type of zone line input (see below), depending on detectors / end-
of-line device (capacitor or resistor), i.e. different threshold levels
etc.
Alarm at short circuit / Not alarm at short circuit (i.e. if short-
circuit on the zone line shall generate a fault or a fire alarm)
Zone (Address optional)
Fire alarm delay / No fire alarm delay
Text (Alarm text when required)
Alert annunciation time channel
Disablement time channel