S1 Supervised (monitored) voltage output, 24V DC
67
, max. 200
mA (Fuse F6).
As default S0-S1 are set to type "Alarm device", "Intermittent 0.8 /
0.8, normally low, supervised and trigger condition "General fire".
Connections and more information, see drawing 128-22.
See also chapter "Programmable voltage outputs (S0-S1)", page 20.
9.2 Control unit output R0
EBL128 has one programmable relay output:
R0 Relay output, NO or NC contacts
programmable.
As default R0 is set to type "Routing equipment" (Fire brigade tx),
Steady (cont.), normally open and trigger condition "Fire brigade tx".
Connections and more information, see drawing 128-23.
9.3 8 relay outputs expansion board 4581
Output 0 – Output 7
Each 4581 board has eight programmable relay outputs:
Output 0 Relay output, NO or NC contacts programmable
Output 1 Relay output, NO or NC contacts programmable
Output 2 Relay output, NO or NC contacts programmable
Output 3 Relay output, NO or NC contacts programmable
Output 4 Relay output, NO or NC contacts programmable
Output 5 Relay output, NO or NC contacts programmable
Output 6 Relay output, NO or NC contacts programmable
Output 7 Relay output, NO or NC contacts programmable
Relay contact ratings: Max. 2A @ 30 V DC.
Connections and more information, see dwg. 128-30.
9.4 Inputs and Outputs expansion board 4583
Output 0 – 1
Expansion board 4583 has two programmable, supervised
(monitored)
66
voltage outputs:
Output 0 Supervised (monitored) voltage output, 24V DC
67
, max.
200 mA (Fuse F1).
Output 1 Supervised (monitored) voltage output, 24V DC
67
, max.
200 mA (Fuse F2).
Connections and more information, see drawing 128-33.
See also chapter "Inputs and outputs expansion board 4583", page 28.
9.5 The 3361 unit outputs Re0 – Re1
Each 3361 unit has two programmable relay outputs:
Re0 Relay output, NO or NC contacts programmable
Re1 Relay output, NO or NC contacts programmable
Relay contacts: max. 1 A @ 30 V DC.