Panasonic Eco Solutions Nordic AB
MEW01622 Rev: - EBL128 Planning Instructions V2.0.x
62
7.1 Control unit Input I0 & Inputs and Outputs
exp. board 4583, Input 0-4
7.1.1 Not supervised
Normally open (R > 2K)
or
Normally closed (R < 2K)
Activation time: >1 sec.
Connections, see drawing 128-22.
7.1.2 Supervised
Each supervised input can be in four different states:
Open circuit (cut-off)
Not activated (quiescent)
Activated
Short-circuit
Depending on the selected logic, Normally open (high resistance) or
Normally closed (low resistance), the following table is valid.
Normally open
(high resistance)
Normally closed
(low resistance)
7.1.2.1 Input line fault
If open circuit (cut-off) or short-circuit is detected on a supervised
input, a fault will be generated in EBL128 and the following fault
message will be displayed:
FAULT: Programmable input
alternatively
FAULT: Programmable input x exp. board x