12 Fire Door Closing function
Programmable outputs
94
can be used for fire door closing. A special
trigger condition is available (no. 44 = Fire Door Closing). Type of
output shall normally be "Control, neutral". One or more alarm points
can control the output, e.g. the detectors on both sides of the fire door.
M
S S
01-01 01-02
Programmable output
Door release magnet
Smoke detector
Fire
door
Fire Door Closing function (ABDL)
In case of one of the following events, the output will be "activated"
(i.e. powerless) and the fire door will close:
Fire alarm (from any of the programmed detectors)
"Test mode" (the zone involved set in test mode)
Fault (i.e. "no answer" from any of the programmed
detectors
95
)
Disablement (any of the programmed detectors or the
involved zone(s)).
A definite time every day, if programmed via EBLWin.
(The output will be activated for 20 seconds.)
Via a programmable input (trigger condition no. 9 = Door
Closing Test Input). (The output will be activated for 20
seconds.)
NOTE!
For safety reasons should an I/O unit 3361 output not be used.
94
If
there is short-circuit or a double break on the COM loop, the I/O unit
cannot be "ordered" to activate the output, i.e. the door will not be
closed.
If a magnet contact is available, it is possible to get a "closed fire door
verification" via the Interlocking function. In this case, Type of in-
/output has to be "Interlocking in-/output". See also chapter
"Interlocking function", page 88.
94
It is recommended but in the DBI (Danish) convention, must only EBL128
outputs R0 and S0-S1 as well as the COM loop unit 3364 be used and "Type
of output" has to be "Control neutral".
95
E.g. a faulty detector, two breaks or short-circuit on the COM loop.