MEW01622 Rev: - EBL128 Planning Instructions V2.0.x
33
See also chapter "Current consumption", page 162 and drawing 128-
11.
The following units can be connected to the COM loop in NORMAL
mode (if nothing else is stated):
NOTE!
4301 in NORMAL mode = 3304 in NORMAL mode.
4300 in NORMAL mode = 3316 in NORMAL mode.
3361 The I/O Unit for Fan control is used with the Fan control panel
4593 only.
AAFC The Alarm Acknowledge Facility Control is used on the
Australian market only.
Obsolete loop units (listed below) can be found in old installations and
can be used in EBL128 installations as well.
2300 & 2304 plugged in base 2312.
2304 = 4301 & 3304 in 2312 mode.
NOTE! When one or more of the Obsolete loop units listed above are
used on a COM loop, only technical address 1-127 can be used.
Address setting / Technical address
Each COM loop unit has to have a unique technical address (001-
255). This address and the mode are set with an Address Setting Tool
3314 / 4414. For EBL128 is the NORMAL mode used (default) if
nothing else is stated. To set the detectors 440x in Advanced mode
the Address Setting Tool 4414 has to be used.