Panasonic Eco Solutions Nordic AB
MEW01622 Rev: - EBL128 Planning Instructions V2.0.x
49
Figure 9. Four isolators connected to a COM loop gives five
loop segments, i.e. Segment A (A-00), B (00-01), C (01-02), D
(02-03) and E (03-B). If more isolators have to be added, the
sequence numbers have to be updated (via EBLWin), e.g. if
one isolator is put in between isolator no. 00 and no. 01 in the
figure, the new isolator has to have sequence number 01 and
the old no. 01 has to be changed to no. 02 and so on.
Short circuit / cut-off (break) on the COM loop
See chapter "COM loop", page 17. See also chapter "Fault messages"
in the EBL128 Operating Instructions.