Panasonic Eco Solutions Nordic AB
MEW01622 Rev: - EBL128 Planning Instructions V2.0.x
78
10.5.1.4 Other
35 Indication Fire Brigade Tx Activated
36 Indication Fault Tx Activated
37 General Fault
38 General Mains Fault
39 Reset Pulse Zone Address (+Zone no. +Address)
40 Time Channel Activated (+Time channel name / no.)
41 Alert Annunciation Activated
42 Alert Annunciation Acknowledged
43 Door Open
44 Fire Door Closing (+Zone no. +Address)
45 General Service Signal
46 Fire brigade Tx
47 Door Open Control Unit (+Control unit)
48 Extinguishing System Fault
49 Extinguishing System Released
50 Activated Key Cabinet
51 Fault Control Unit (+Control unit)
52 Consecutive Fault Control Unit (+start Control unit and
stop Control unit)
53 Zone Fault (+Zone no.)
54 External Fault (+ext. fault)
55 Technical Warning (+techn. warning)
56 General Technical Warning
Comments to the trigger conditions (functions):
Alarm
1 Fire alarm. For more information regarding fire alarm,
see EBL128 Operating Instructions MEW01623. Output
is activated when the specified Zone is in alarm.
2 See 1. Output is activated when the specified alarm point
is in alarm.
3 See 1. Output is activated when any alarm point or Zone
is in alarm.
4 See 1. Quantity (1-10): "1" means one unit in alarm is
required, "2" means two units in alarm are required to
activate the output and so on.
5 Pre-warning.
For more information regarding pre-
warning, see EBL128 Operating Instructions
MEW01623. Output is activated when the specified
Zone is over the pre-warning level.
Not valid for the 3364 outputs (VO0-VO2).
The trigger condition is true as long as the pre-warning level is exceeded.
It is also true as long as the fire alarm level is exceeded even if the option
pre-warning detection is disabled (via EBLWin).