MEW01622 Rev: - EBL128 Planning Instructions V2.0.x
85
Output: Voltage output S0
Control expression: Pre Warning Zone (10)
Explanation: Pre-warning activated in zone no. 10 will
activate the output S0.
Example 2
Output: Relay output R0
Control expression: General Control disabled AND NOT Door
Open
Explanation: Controls disabled via menu H2/B7 will
activate the output R0 when the door in
EBL128 is not open (i.e. when it is closed).
Example 3
Output: Voltage output VO0
Control expression: Fire Alarm Zone (23) AND Fire Alarm Zone
(24) AND NOT General Fault
Explanation: Fire alarm activated in zone 23 and zone 24
will activate the output VO0 only if there are
no faults in the system at the same time.
Example 4
Output: Voltage output S1
Control expression: Consecutive Fire Alarm (10,10,10,19,1) OR
Consecutive Fire Alarm (10,21,10,40,1)
Explanation: Fire alarm activated by one of the alarm
points in zone 10 addresses 10-19 or by one
of the alarm points in zone 10 addresses
21-40 will activate the output S1 (i.e. the
alarm point in zone 10 address 20 will not
activate the output S1).