1 Product overview
1.6 Reset tact switch
A small tact switch within the housing on the top side can be used to restart or to reset the
FP-I4C unit.
To restart or to reset the unit, use a paperclip or similar and press the tact switch 3 times
within 3s. The yellow USR LED starts flashing (heartbeat 1/s).
To restart the unit, press the tact switch again for 3 to 6s.
To reset the unit to the factory settings, press the tact switch again for at least 6s. The unit
will be restarted and all user data are removed.
1.7 Devices supported by USB host ports
The USB host ports support the FP series PLCs and GT series HMIs listed in the following
targeted peripheral list.
Commercial USB flash drives and hard disks (max. 500mA on upper USB connector) can
also be connected.
Panasonic GT USB driver ver. 1.0
Model: GT series, manufacturer: Panasonic Electric Works, Ltd., vendor ID: 0x0986,
product ID: 0x0310
Panasonic FP series USB driver
Model: PLC FP0H, FP7, FP0R, manufacturer: Panasonic Electric Works, Ltd., vendor ID:
0x0986, product ID: 0x0320
Panasonic Eco-POWER METER
Model: Eco-POWER METER, manufacturer: Panasonic Electric Works, Ltd., vendor ID:
0x04da, product ID: 0x4201
Panasonic FP-X series USB driver
Model: CP210x UART Bridge, e.g. FP-X, manufacturer: Cygnal Integrated Products,
vendor ID: 0x10C4, product ID: 0xEA60