3 Wiring
3 Wiring
3.1 Connection to PLC TOOL port using cable AIGT8192
Use the cable AIGT8192 to connect the FP-I4C unit to the 5-pin mini DIN male TOOL port of
an FP0R, FPƩ, FP-X, or FP2SH type PLC.
Use either COM1 or COM2 depending on your setting for “Service control interface” in the
Web interface of the FP-I4C unit.
The cable AIGT8192 can be ordered as an accessory.
Using COM1:
1
2
3
5
4
R (COM1)
G1 (COM1)
S/- (COM2)
F1
S (COM1)
G1 (COM1)
S/- (COM2)
S/- (COM2)
F2
R/+ (COM2)
R/+ (COM2)
E
G2 (COM2)G2 (COM2)
AIGT8192, 5-pin mini DIN male (left) and FP-I4C 16-pin connector (right)
Using COM2:
1
2
3
5
4
R (COM1)
G1 (COM1)
S/- (COM2)
F1
S (COM1)
G1 (COM1)
S/- (COM2)
S/- (COM2)
F2
R/+ (COM2)
R/+ (COM2)
E
G2 (COM2)G2 (COM2)
FP-I4C 16-pin connector (left) and AIGT8192, 5-pin mini DIN male (right)
3.2 Connection to PLC COM port
Wire the 16-pin connector of the FP-I4C unit directly to the COM port of an FP0R, FP-X,
FPƩ, FP0H, or FP7 type PLC.
Use either COM1 or COM2 depending on your setting for “Service control interface” in the
Web interface of the FP-I4C unit.