45
MEWTOCOL
command code
Data item Data
RD/WD DT00260 Backlight 0000H: All are backlit
0001H: Only PV display is backlit
0002H: Only SV display is backlit
0003H: Only action indicators are backlit
0004H: PV+SV displays are backlit
0005H: PV+ action indicators are backlit
0006H: SV+ action indicators are backlit
RD/WD DT00262 PV color 0000H: Green
0001H: Red
0002H: Orange
0003H:WhenAlarm ON, Green Red
0004H:WhenAlarm ON, Orange Red
0005H: PV color changes continuously
0006H: PV color changes continuously
+ Alarm ON: Red
RD/WD DT00264 PV color range Set value, Decimal point ignored
RD/WD DT00266 Backlight time Set value
WD DT00324 Key operation change flag clearing 0000H: No action
0001H: All clearing
RD DT00356 PV (Process variable) Decimal point ignored
RD DT00358 OUT1 MV Decimal point ignored
RD DT00360 OUT2 MV Decimal point ignored
RD DT00362 SV (When SV rises or falls) Decimal point ignored
RD DT00366 Status flag
0000 0000 0000 0000
2
0
: OUT1 0: OFF, 1: ON
(DC current output type: Not fixed)
2
1
: OUT2 0: OFF, 1: ON
2
2
: Alarm 1 output 0: OFF, 1: ON
2
3
: Alarm 2 output 0: OFF, 1: ON
2
4
: Not used, always 0
2
5
: Not used, always 0
2
6
: Heater burnout alarm 0: OFF, 1: ON
(When Sensor burnout, 0: OFF)
2
7
: Not used, always 0
2
8
: Overscale 0: OFF, 1: ON
2
9
: Underscale 0: OFF, 1: ON
2
10
: Control output OUT/OFF
0: ON, 1: OFF
2
11
: During Auto-tuning/Auto-reset
0: OFF
1: During Auto-tuning/Auto-reset
2
12
: OUT/OFF key function
0: OUT/OFF function, 1: Auto/Manual control
2
13
: Not used, always 0
2
14
: Auto/Manual control
0: Automatic control, 1: Manual control
2
15
: Change in key operation
0: No, 1: Yes
RD DT00368 CT1 current value Decimal point ignored
RD DT00370 CT2 current value Decimal point ignored